Patients set of classic care (UBS 2100)

Contain:

>HOSPITAL SET FOR SURGERY(UBS 2210)
>HOSPITAL SET FOR DIALYSIS (UBS 2220)
>HOSPITAL SET FOR CORONARY UNITS (UBS 2230)


Patient during their stay in the hospital most of the time spent in hospital room.




In the intensive care rooms,quality of illuminance is not of primary significance,as it is in the case of classic treatment hospital rooms.It is more important to make optimal conditions for the patients(often in critical health condition) care.

We distinguish three types of the hospital care hospital sets, depending on the design, number and type of used outlets:
- hospital set for surgery (UBS 2210)
- hospital set for dialysis (UBS 2220)
- hospital set for coronary units (UBS 2230)

Coronary unit hospital set (UBS 2230) can be mounted only on the ceiling, surgery hospital set can be mounted on the ceiling (UBS 2212) and on the wall (UBS 2211), dialysis hospital set can be mounted on the wall (UBS 2221) and on the ceiling (UBS 2222).

ILLUMINATION

Illumination of the hospital rooms should support the patient recuperation and easy adaptation to the hospital atmosphere.

General illumination of the hospital room is exclusively realized as indirect one. Illuminating source is positioned above the patient bed, to obtain required even distributed illumination in the room and the avoidance of shadows.

Every bed is equipped also with reading lighting (direct lighting). This lighting is beamed, so the disturbance of the neighbor patients is avoided.

Illuminaton in the rooms with beds should enable the patient examination and therapy practice (working lighting), together with orientation and surveillance lightings.

Technical requirements concerning the illumination are given in the DIN 5035 part 3 (“Artificial light internal illumination - Recommendations for the hospital illumination”) and are given in the following table:

TYPE OF ILLUMINATION

LUMINANCE

General (indirect) lighting 100, measured on horizontal surface 0.85m above the floor
Reading (direct) lighting 200, measured on slanted surface 0.3 x 0.9m, angle of 75°
Examination (working) lighting 300, measured on horizontal surface 0.85m above the floor
Surveillance lighting circa 5, measured on horizontal surface 0.85m above the floor
Orientation lighting mounted near the room entrance

GENERAL ILLUMINATION

This illumination is realized exclusively as indirect illumination. The hospital set UBS 2100 is composed of two fluo tubes (36W) with reflector which distributes light towards ceiling and wall. In this manner, even illumination of patient room without shadows is achieved. Reflector with fluo tubes is covered with transparent Plexiglas, and exchange of fluo lamps is quick and simple. Measured value of luminance for this type of illumination is 120 lx, according to the DIN 5035.


READING ILLUMINATION

Reading illumination or direct lighting is realized with one fluo lamp of 18W, with reflector that distribute light only to the underlying bed. This type of lamp is covered with plastic raster. For exchange of fluo tube, one need to dismantle plastic raster, and for the starter taking out, the service personnel should raise Plexiglas panel of the general lighting reflector. Measured value of luminance according to the DIN 5035 is 210 lx.

 

EXAMINATION ILLUMINATION

This lighting should enable good vision conditions during the examinations and other treatments in the patient curing in his bed.In this case, direct and indirect lightings should be switched on simultaneously.This results in luminance of 320 lx on the surface 0.85m above the floor, giving very good vision conditions.

ORIENTATION LIGHTING

This type of illumination enables the personnel to freely circulate in the patient room and to survey the patients in night conditions.This lighting is realised with common bulb of 15W, in set of UBS 2100 type. Measured luminance value is 5 lx, that meets DIN 5035 standard.

The patient set UBS 2100 HF is an improved set that utilizes fluo lamps with high frequency transformers with regulation possibility.This solution eliminates light flickering, reduces power consumption, improves luminance and prolongs tube life.

Oba izvođenja bolesničkog seta hospitalne nege (UBS 2100, UBS 2100 HF) realizovana su sa standardnim štapastim cevima, što olakšava posao službi održavanja u bolnici.

ELECTRIC POWER OUTLETS

Besides the illumination of the patient room,hospital set UBS 2100 supplies necessary mains power and low DC voltage connectors to the patient bed. All mains power and low voltage outlets are connected to the main (central) terminal that is positioned on the one end of the hospital set.

 

THE MAINS POWER TERMINALS

     



Connections for power electric devices from the grounded mains power sypply
Color of device: White
Color of mask: white or silver
Range: 250V/16A




Connections for power electric devices from the grounded inverter power sypply
Color of device: Green
Color of mask: white or silver
Range: 250V/16A

 

Connections for power electric devices from the grounded aggregate power sypply
Color of device: Red
Color of mask: white or silver
Range: 250V/16A

potential equalizer connector according to the DIN 42801 standard.
The potential equalizer connectors are galvanic insulated from the housing, connected internally with strained yellow-green lead (cross-section is 4 square millimeters), and tied to the central clamp terminal.

Both grounded outlets are rated at 250V/16A.

LOW POWER OUTLET




All beds are equipped with telephone/computer connector
Color of device: White/black
Color of mask: white or silver
Category: 6




Type of terminal is dependent on used hospital information system (BIS 2010, BIS 2020, BIS 2030)

Connecting Terminal (PT 2001A)
Color of device: silver/blue
Color of mask: white or silver

 

Exemple for bed panel type (KP 2004A) (BIS 2020, BIS 2030)
Color of device: silver/blue
Color of mask: white/silver

The hand-set differs in accordance whether the BIS enables light/audio signalization, speech communication or listening to the musical or educational programs. In any case it contains a reading lighting on/off push-button with indication.

 

MEDICAL GASSES CONNECTORS




The hospital set UBS 2100 contains two copper tubes (8mm dia x 1mm) for oxygen and comprimed air distribution and one copper tube (12mm dia x 1mm) for the vacuum distribution.
The medical gasses outlets are situated in the separate channel adjacent to the power and low power channels, or in the separate boxes inter-connected with smaller channels.
Factory mounted gas outlets are DRÄGER fabricated, but other types can be used on the customer request. Mounted outlets are connected to the central terminal with copper tubes and corresponding fittings.Used copper tubes are attested for this purpose, and all installation is checked on leaking with pressure of 10 bar.
Number and type of medical gasses outlets for one patient place depend on the type of the intended hospital unit (surgery, gynecology etc.).
Depending on the number and type of medical gasses outlets, we distinguish two variants of the hospital sets for the hospital treatment:
-Classic treatment hospital set (UBS 2110)
-Semi-intensive care hospital set (UBS 2120)
If medical gases supply exists, one and two bed hospital sets possess one group of outlets (oxygen, compressed air), but three bed hospital set possess two groups of outlets.


LIGHTING TERMINALS

The hospital set is composed of two longitudinal aluminum profiles. There are all power and low power outlets on the upper profile, while the lower profile contains indirect and direct lighting lamps.

The indirect lighting can be switched on with an entrance door switch, connected to the upper profile central terminal. Direct lighting is activated with hand-set (RS) or electronic switch (EP).

Electronic switch for the direct lighting activation/deactivation, galvanic insulates the patient from the mains live lead. It is mounted in the x, on the lower side of the hospital set, for easy approach.